  • Standard: IEC60269-6,UL248-19,GB/T13539.6
  • Breakingcapacity: 50kA
  • Construction: Cylindrincal
  • With Forced Arc Extinguishing

Features

  • Standard: IEC60269-6,UL248-19,GB/T13539.6
  • Breakingcapacity: 50kA
  • Construction: Cylindrincal
  • With Forced Arc Extinguishing

Dimensions (mm)

Wrpv 32l (4)

Fuse cold-state resistance andpower loss

Product Model Rated current(A) Watts Loss1In (W) Energy  Integralsl²t(A²s)
Pre-Arcingl²t Total  I²t
WRPV-
32L
1 2.1 2.3 3.1
2 2.3 7.4 10
3 2.5 13 18
4 2.5 27 37
5 2.5 41 56
6 2.6 58 79
8 2.8 11 82
10 3.0 19 144
12 3.1 33 246
15 3.5 59 432
16 4.0 63 460
20 4.5 112 822
25 4.6 197 1440
30 5.4 304 2220
32 6.2 325 2370
35 7.5 390 2844

Technical Parameters

Fuse Link Type gPV Rated Voltage(V) Rated current(A) Dimensions (mm) Watts Loss(W)
WRPV-32L DC1500V 1,2,3,4,5,6,8,10,12,15,16,20,25,30,32,35 10×85 ≤7