WRPV-30

  • Standard: IEC60269-6,UL248-19,GB/T13539.6
  • Breakingcapacity: 33kA
  • Construction: Cylindrincal
  • With Forced Arc Extinguishing

Features

  • Standard: IEC60269-6,UL248-19,GB/T13539.6
  • Breakingcapacity: 33kA
  • Construction: Cylindrincal
  • With Forced Arc Extinguishing

Dimensions (mm)

Dimensions (mm)

Fuse cold-state resistance andpower loss

Product
Model
Rated
current(A)
Watts Loss
(W)
Energy  Integralsl²t(A²s)
Pre-Arcing Total at 1000V
WRPV-
30
1 1.30 1.1 3.9
2 1.36 1.5 5.2
3 1.42 2.4 8.6
4 1.58 2.9 11.4
5 1.83 6.7 25.7
6 1.84 10.5 40
8 1.86 15.2 57
10 2.08 20 92
12 2.62 30.4 143
15 2.95 45.6 205
20 3.12 79.8 366
25 3.46 114 599
30 3.78 143 713
32 3.95 148 722

Technical Parameters

Fuse Link
Type gPV
Rated Voltage(V) Rated current(A) Dimensions(mm) Watts Loss(W)
WRPV-30 DC1000V 1,2,3,4,5,6,8,10,12,15,16,20,25,30,32 10×38 ≤4

Technical Parameters

Fuse Holder Type Fuse link size Rated Voltage(V) Rated current(A) Watts Loss(W)
WRPV-30D 10×38 1000Vdc 32A 4W