WREV-MM

This series of fuses are suitable for short circuit and overload protection of electric vehicle drive power system, power conversion system, energy storage and power system, variable frequency controller, charging pile, and other vehicle devices and equipment in lines with DC rated voltage up to 1000V and rated current up to 800A. The rated breaking capacity is up to 50kA. The fuses conform to the national standard GB/T13539.7 and the International Electrotechnical Commission Standard IEC60269-7.

WREV  Fast DC fuse for new energy protection.

1.Application

This series of fuses are suitable for short circuit and overload protection of electric vehicle drive power system, power conversion system, energy storage and power system, variable frequency controller, charging pile, and other vehicle devices and equipment in lines with DC rated voltage up to 1000V and rated current up to 800A. The rated breaking capacity is up to 50kA. The fuses conform to the national standard GB/T13539.7 and the International Electrotechnical Commission Standard IEC60269-7.

2.Normal working conditions

2.1 The effect of current

The upper limit of ambient air temperature should not exceed 90℃; the lower limit of ambient air temperature should not be lower than -50℃; the altitude of the installation site should not exceed 2000m (if you want to exceed this 2000m, you need to indicate the requirements, and the company can design and develop according to customer requirements).

fuse link derating table for installation

Installation altitude(m) Percentage of current derating (A) Percentage of Insulation performance derating(V)
2000 100% 100%
3000 95% 90%
4000 90% 80%
5000 85% 70%

For example: the rated current is 18A and the installation site altitude is 5000m, the actual selection is 18*85%≈15.3A.

 

2.2 The effect of Voltage

The rated voltage of photovoltaic fuses does not need to be derated for installation altitudes not exceeding 5000m, but it is affected by air pressure on the power frequency withstand voltage and insulation performance to a certain extent. The test voltage of DC 1001-1500V is 3820V, and Our products reach at least 6000V, so here is no need to consider.

 

2.3 The effect of temperature

The following figure shows a typical curve of the influence of ambient temperature on current carrying capacity:

The Effect Of Temperature

For example: In some applications, the ambient temperature is 20°C, and the rated current of the photovoltaic (gPV type) fuse is selected as 63A. Now, the above-mentioned fuse is often used in a high temperature environment of 70 ℃, then the fuse must be derated. The environmental bearing capacity curve A in the figure shows that the percentage of the rated operating value at 70°C is 0.78, that is to say, the rated current value of the fuse should be reselected:

图片1

Choose 80A according to the standard current level of the fuse

 

3.Use category

“aBat” is Fast DC fuse for new energy protection.

4.Structural features

The variable cross-section melt made of silver flakes is encapsulated in a high-strength melt tube. The melt tube is filled with chemically treated high-purity quartz sand and special treatment chemicals as the arc extinguishing medium. The welding and the contacts are firmly electrically connected.

 

5.The main technical parameters

figure 1

图片2

Fuse

type

Size Rated Voltage

 

Rated Current

(A)

figure

Dimensions/Size(mm)

aBat A B C D E F G H J
WREV-MM 02B102

DC

1000V

35-100 1 122 106 98.5 82 19 25 8.5 4 12
03B105 63-250 125 108 101 82 24 31 8.5 5 12
04B113 160-350 141 121 105 85 25 38 10.5 6 18
05B114 250-500 142 121 106 84 38 51 10.5 6 18
06B138 400-800 186 154 122 90 50 63 14 10 30

6.Fuse cold resistance and power dissipation

Fuse Type Rated current(A) 1In(W) Pre-arcing I2t Total I2t remarks
WREV-MM 35 6.2 181 1216
40 7.6 285 1606
45 8.6 321 1805
50 9.5 428 2375
60 14 675 4133
70 14 808 5320
80 15 1045 6337
90 16 1758 10450
100 17 2242 12065
125 19 3325 20425
150 27 4769 25270
175 29 8835 38950
200 30 15295 58425
225 39 19095 101650
250 46 24035 109250
275 48 26439 120175
300 50 25745 156750
325 53 27930 169813
350 57 40850 220400
400 63 68400 306850
450 76 75050 313500
500 90 100700 346750
600 105 156750 505400
700 145 309700 665000
800 174 401850 845500