WRPV-32L

  • Standard: IEC60269-6,UL248-19,GB/T13539.6
  • Breakingcapacity: 50kA
  • Construction: Cylindrincal
  • With Forced Arc Extinguishing

Features

  • Standard: IEC60269-6,UL248-19,GB/T13539.6
  • Breakingcapacity: 50kA
  • Construction: Cylindrincal
  • With Forced Arc Extinguishing

Dimensions (mm)

Wrpv 32l (4)

Fuse cold-state resistance andpower loss

Product ModelRated current(A)Watts Loss1In (W)Energy  Integralsl²t(A²s)
Pre-Arcingl²tTotal  I²t
WRPV-
32L
12.12.33.1
22.37.410
32.51318
42.52737
52.54156
62.65879
82.81182
103.019144
123.133246
153.559432
164.063460
204.5112822
254.61971440
305.43042220
326.23252370
357.53902844

Technical Parameters

Fuse Link Type gPVRated Voltage(V)Rated current(A)Dimensions (mm)Watts Loss(W)
WRPV-32LDC1500V1,2,3,4,5,6,8,10,12,15,16,20,25,30,32,3510×85≤7

Wrpv 32l (3)

Time Current Curve

Wrpv 32l (2)

 

GET FREE QUOTE

We are committed to providing professional fuse and circuit protection solutions for renewable energy, electric vehicles, industrial power systems and electrical infrastructure.
Scroll to Top

Contact Us