WRES-MP DC1500V- 3000A

This series of fuses are suitable for short circuit and overload protection of electric vehicle drive power system, power conversion system, energy storage and power system, variable
frequency controller, charging pile, and other vehicle devices and equipment in lines with DC rated voltage up to 1500V and rated current up to 3000A. The rated breaking capacity is up to 250kA. The fuses conform to the national standard GB/T13539.7 and the International Electrotechnical Commission Standard IEC60269-7.

Application

This series of fuses are suitable for short circuit and overload protection of electric vehicle drive power system, power conversion system, energy storage and power system, variable
frequency controller, charging pile, and other vehicle devices and equipment in lines with DC rated voltage up to 1500V and rated current up to 3000A. The rated breaking capacity is up to 250kA. The fuses conform to the national standard GB/T13539.7 and the International Electrotechnical Commission Standard IEC60269-7.

Normal working conditions

1、The effect of current

The upper limit of ambient air temperature should not exceed 90℃; the lower limit of ambient air temperature should not be lower than -50℃; the altitude of the installation site should not exceed 2000m (if you want to exceed this 2000m, you need to indicate the requirements, and the company can design and develop according to customer requirements).

fuse link derating table for installation

Installation altitudem Percentage of current derating (A) Percentage of Insulation performance derating(V)
2000 100% 100%
3000 95% 90%
4000 90% 80%
5000 85% 70%

For example: the rated current is 1800A and the installation site altitude is 5000m, the actual selection is 1800*85%≈1530A.

2、The effect of Voltage

The rated voltage of photovoltaic fuses does not need to be derated for installation altitudes not exceeding 5000m, but it is affected by air pressure on the power frequency withstand voltage and insulation performance to a certain extent. The test voltage of DC 1001-1500V is 3820V, and Our products reach at least 6000V, so here is no need to consider.

3、The effect of temperature

The following figure shows a typical curve of the influence of ambient temperature on current carrying capacity:

The Effect Of Temperature

For example: In some applications, the ambient temperature is 20°C, and the rated current of the photovoltaic (aBat type) fuse is selected as 63A. Now, the above-mentioned fuse is often used in a high temperature environment of 70 ℃, then the fuse must be derated. The environmental bearing capacity curve A in the figure shows that the percentage of the rated operating value at 70°C is 0.78, that is to say, the rated current value of the fuse should be reselected:

图片

Choose 80A according to the standard current level of the fuse

Use category

“aBat” is Fast DC fuse for new energy protection.

 

Structural features

The variable cross-section melt made of silver flakes is encapsulated in a high-strength melt tube. The melt tube is filled with chemically treated high-purity quartz sand and special treatment chemicals as the arc extinguishing medium. The welding and the contacts are firmly electrically connected.

 

The main technical parameters

Figure 1 Figure 2

Fuse model Rated voltage (V) Rated current (A) Overall dimensions/size (mm)
aBat Drawing number A B C D E MxH
WRES-107K130KN DC1500V 300、350、400、450、500、550、600、630、710、800、900、1000 1 132±2 105±1.5 117±2.5 70±0.8 142±2.5 M16×16
WRES-108K130KN DC1500V 800、900、1000、1100、1250、1300、1400、1500、1600、1700、1800 1 132±2 120±1.5 132±2.5 80±0.8 157±2.5 M16×16
WRES-509K156KN DC1500V 1250、1350、1500、1800、2000、2500、3000 2 See Figure 2

Description of microswitch

Description Of Microswitch

During normal operation, the fuse link is connected between 1 and 3, while 1 and 2 are disconnected. When the fuse link melts, the indicator moves, disconnecting 1 and 3 and connecting 1 and 2, thus achieving remote monitoring. This indicates to electricians that the fuse has melted and needs to be replaced promptly.

 

Power consumption and fuse characteristics table:

Rated current (A) Dissipated power (W) Forearc I2t(A2S) Fuse I2t(A2S) Remark
300 60 146000 384000
315 64 152000 402000
350 69 172000 454000
400 78 198000 524000
450 87 225000 594000
500 99 245000 646000
550 111 264000 698000
600 117 297000 785000
630 162 128000 615000
700 180 218000 1030000
750 193 265000 1250000
800 206 315000 1490000
1000 260 450000 1880000
1250 320 660000 2280000
1350 340 784000 2660000
1500 370 1050000 3470000
1800 430 1570000 4750000
2000 450 2190000 6650000
2500 500 4420000 13300000
3000 550 7700000 23100000

 

Melting characteristic curve

Current(a) Prospection Short Circuit Current Ip(a)